How it works
Calculate nominal battery capacity for a target backup duration from load, DoD and efficiency.
Usable energy = load·hours; nominal capacity = usable energy/(DoD·η)·(1+reserve).
Calculate nominal battery capacity for a target backup duration from load, DoD and efficiency.
Updated September 2026
Calculate nominal battery capacity for a target backup duration from load, DoD and efficiency.
Use verified material data and project geometry. Treat results as planning estimates and compare them with the energy/thermal requirements that apply to the project.
Calculate nominal battery capacity for a target backup duration from load, DoD and efficiency.
Example inputs: Average backup load [kW]: 1.5; Required backup duration [h]: 8; Usable depth of discharge [%]: 90; System efficiency [%]: 92.
Using the sample values built into the calculator, the calculation gives approximately: Required usable battery energy: 12 kWh; Required nominal battery capacity: 15.94 kWh.
Calculation method: Usable energy = load·hours; nominal capacity = usable energy/(DoD·η)·(1+reserve).
Before using the result: Also check battery power, inverter surge, temperature, degradation, cycle life and safety.
Calculate nominal battery capacity for a target backup duration from load, DoD and efficiency.
Key inputs to verify include: Average backup load [kW], Required backup duration [h], Usable depth of discharge [%], System efficiency [%].
Use the result as a transparent planning or checking aid. Final design, code compliance, supplier selection and project-specific decisions still need to be verified where applicable. Also check battery power, inverter surge, temperature, degradation, cycle life and safety.