How it works
Estimate sensible heating or cooling duty from airflow and temperature difference.
Q = ρ·cp·V̇·ΔT, airflow converted from m³/h to m³/s.
Estimate sensible heating or cooling duty from airflow and temperature difference.
Updated September 2026
Estimate sensible heating or cooling duty from airflow and temperature difference.
Use verified material data and project geometry. Treat results as planning estimates and compare them with the energy/thermal requirements that apply to the project.
Estimate sensible heating or cooling duty from airflow and temperature difference.
Example inputs: Airflow [m³/h]: 5 000; Air temperature change ΔT [K]: 10; Air density [kg/m³]: 1.2; Air specific heat cp [kJ/kgK]: 1.005.
Using the sample values built into the calculator, the calculation gives approximately: Sensible HVAC duty: 16.75 kW.
Calculation method: Q = ρ·cp·V̇·ΔT, airflow converted from m³/h to m³/s.
Before using the result: Sensible load only; latent moisture load and system gains/losses may also govern.
Estimate sensible heating or cooling duty from airflow and temperature difference.
Key inputs to verify include: Airflow [m³/h], Air temperature change ΔT [K], Air density [kg/m³], Air specific heat cp [kJ/kgK].
Use the result as a transparent planning or checking aid. Final design, code compliance, supplier selection and project-specific decisions still need to be verified where applicable. Sensible load only; latent moisture load and system gains/losses may also govern.