Calculate single- or three-phase current from real power, voltage, power factor and efficiency.
I1φ = P/(V·PF·η); I3φ = P/(√3·V·PF·η).
Calculate single- or three-phase current from real power, voltage, power factor and efficiency.
Updated September 2026
Calculate single- or three-phase current from real power, voltage, power factor and efficiency.
Use verified material data and project geometry. Treat results as planning estimates and compare them with the energy/thermal requirements that apply to the project.
Calculate single- or three-phase current from real power, voltage, power factor and efficiency.
Example inputs: System: Three phase; Real load power [kW]: 15; Line voltage [V]: 400; Power factor cosφ: 0.9.
Using the sample values built into the calculator, the calculation gives approximately: Load current: 26.15 A; Apparent power: 18.12 kVA.
Calculation method: I1φ = P/(V·PF·η); I3φ = P/(√3·V·PF·η).
Before using the result: Calculated load current is not a cable ampacity selection; apply installation and protection rules separately.
Calculate single- or three-phase current from real power, voltage, power factor and efficiency.
Key inputs to verify include: System, Real load power [kW], Line voltage [V], Power factor cosφ.
Use the result as a transparent planning or checking aid. Final design, code compliance, supplier selection and project-specific decisions still need to be verified where applicable. Calculated load current is not a cable ampacity selection; apply installation and protection rules separately.